From HFML-FELIX Wiki
Jump to: navigation, search
  1. Controlroom FELIX console
    1. Turn off GUN RF TIMING ON
    2. Turn off 3 GHZ RF TIMING ON
    3. If FELICE is not running:
      1. Turn off GUN HV ON
      2. Turn off GUN RF ENABLE
      3. Turn off 3 GHZ ENABLE
      4. Turn off CHARGE MODULATOR
      5. Turn off SLINGERCIRCUIT ON
    4. Close vacuum line 1 or 2B
    5. Set the timer FELIX BEAM PULSE to 2 Âµs
    6. Set Repetition rate to 1 Hz
    7. Set Repetition rate to 1 Hz
    8. If beam line was FEL2:
      1. Switch magnet 2B20_25 to Main power off
    9. If FELICE is running:
      1. Turn off timer S2 FELIX accel SP 2
    10. If FELICE is not running:
      1. Close 'all vacuum valves
  2. Controlroom Building console
    1. If FLARE and FELICE are off:
      1. Turn MASTER KEY from RUN to SWEEP
  3. Controlroom FLARE console
    1. If FLARE is off:
      1. Turn off the FLARE solenoids
    2. If FELICE is off: proceed to FTA
      1. proceed to FTA Fel Technical Area modulator cabinets and repeat for both modulators (East and West):
        1. Push LOCAL to select local control
        2. Turn off high voltage
        3. Turn off line
        4. Turn off klystron
        5. Turn off cooling
        6. Turn off the high voltage power supplies (two per modulator)
      2. FTA COFFEE cabinet
        1. Turn off the East 3 GHz amplifier (round green power button)
        2. Turn off the gun RF amplifier and power supply
        3. Turn off the prebuncher power supply
      3. FTA near exit:
        1. Turn off the West 3 GHz amplifier (round green power button) high on the wall
        2. Turn off the beam optics magnet power supplies (square green buttons)
        3. Turn of the lights in FTA
  4. FX0 Building lighting console
    1. If you are the last to leave:
      1. Turn off all the lights
    2. If another operator is present: check that the other operator knows how to turn off the lights